How to fix adjust co2 at partial load: step by step
- Press the button until the service indicator shows 0 (lower heating output).
- Measure CO2 at the flue gas pipe.
- If needed, unscrew cover cap B and turn adjustment screw A in small steps with a Torx 40 driver. Clockwise increases CO2; counter-clockwise decreases CO2.
- Record the reading in the maintenance record on page 158.
- Start the upper and lower heating outputs again via the burner control unit and recheck.
- Press the two buttons together for more than 2 seconds to return the burner to operating mode.
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 67. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.