Viessmann Boiler: Adjust CO2 at partial load

Updated · by Aurora Star Tech Inc.

Adjust CO2 at partial load on a Viessmann boiler: Adjusts the CO2 level at lower heating output and returns the boiler to operating mode.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner

How to fix adjust co2 at partial load: step by step

  1. Press the button until the service indicator shows 0 (lower heating output).
  2. Measure CO2 at the flue gas pipe.
  3. If needed, unscrew cover cap B and turn adjustment screw A in small steps with a Torx 40 driver. Clockwise increases CO2; counter-clockwise decreases CO2.
  4. Record the reading in the maintenance record on page 158.
  5. Start the upper and lower heating outputs again via the burner control unit and recheck.
  6. Press the two buttons together for more than 2 seconds to return the burner to operating mode.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More service & test modes tips for boiler

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 67. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.