Service & test modes: Boiler tips (part 2 of 10)
Short, practical technician tips on service & test modes for boiler. Check each one against the manual for your exact model before acting.
View the error history
NTI · TRX150
The HISTORY button shows the last 10 errors stored by the boiler.
- Press the HISTORY button.
- Scroll through the stored errors.
- Note the codes before clearing any lockout.
Combustion analysis port access
Rinnai · I-Series Plus condensing combi boiler
Combustion analysis must be done by a trained and qualified professional. The CO2 or O2 reading is taken in the exhaust with the boiler held at forced high or low fire.
- Remove the front panel by removing the two screws that hold it.
- Remove the clamp holding the combustion analysis port cap.
- Remove the cap and insert the gas analyzer probe into the port.
- Put the boiler into forced high fire or low fire as needed (see section 12.12 Forced Hi/Low Fire Modes).
- Measure CO2 or O2 in the exhaust.
- Remove the probe, refit the cap and clamp, then reinstall the front panel with the two screws.
Display diagnostic codes
Rinnai · I-Series Plus combi boiler
Shows the last nine maintenance codes one after the other.
- Press and hold the Domestic Hot Water button for two seconds, then the Up button, holding both at the same time.
- The last nine maintenance codes display and flash one after the other.
- To exit, press and hold the Domestic Hot Water button and the Up button together for two seconds.
Force the burner on for combustion checks (SERV function 1)
Rinnai · E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
SERV chapter test functions: 1 = burner at adjustable load, 2 = fan, 3 = pump, 4 = showroom mode. Function 1 is what you use for the O2 / CO2 check and the ionization reading.
- Enter C123, press MODE until SERV
- Press STEP to pick function 1
- Raise the load with +; hold - to go down to OFF, which ends the test
- Target O2 at minimum 4.4 % on natural gas, 4.8 % on propane; ionization at least 4 uA
Forced high and forced low fire test modes
Rinnai · I-Series Plus combi boiler
Licensed professional test mode for forcing the burner to high or low fire.
- Remove the front panel by removing the two screws.
- Locate the PC board on the lower left side.
- Press and hold the right-side black button to show FL (forced low fire).
- Press the right-side black button again to show FH (forced high fire).
- Press the right-side black button again to return to normal operation.
- Note: the first steps for entering this mode are not fully legible on the extracted page.
Ignition safety test (forced E02 lockout)
Rinnai · E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
Proves the flame-failure lockout works. Expect one start plus four retries, then a flashing E02.
- Unplug the ionization cable
- Start SERV function 1
- Wait for the start attempts to finish and E02 to flash
- Reconnect the cable and reset the boiler
Read the technical read-out and error history
Rinnai · E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
Hold STEP 5 s to switch the display to the technical read-out (status digit left, supply temperature / water pressure right). The ERRO chapter stores the last error (Err.L) and five earlier ones (Err.1 to Err.5) with status, T1, T2, kW and pump %.
- Hold STEP 5 s to toggle the technical read-out
- For history: enter C123, press MODE until ERRO, STEP through Err.L to Err.5
Start deaeration on the PC board
Rinnai · I-Series Plus IP060160C
Deaeration purges air from the boiler and system after filling or service. Use the SW2 button on the PC board, or the control panel on first install.
- Press and hold the SW2 button on the PC board.
- Wait for the Maintenance Mode icon to show on the controller. Deaeration starts.
- On first install you can instead press and hold the DHW button, then press the CH button at the same time, without removing the front panel.
SW3 button on PC board for descaling mode
Rinnai · All I-Series Plus condensing combi boilers
The SW3 button on the PC board (lower left side) starts and stops the descaling mode. Press it again to cancel. You can also cancel using the Switching Operation Mode button on the controller.
- Remove the boiler front panel by removing the two screws.
- Locate the PC board on the lower left side of the unit.
- Press SW3 to enter descaling mode, or press again to return to normal mode.
SW3 button starts and exits descaling mode
Rinnai · I-Series Plus condensing combi boiler
The SW3 button on the PC board is used to enter descaling mode and to return the unit to normal mode after the cycle.
- Press SW3 on the PC board to start descaling mode.
- Press SW3 again after the rinse to return to normal mode.
View boiler performance data
Rinnai · I-Series Plus condensing combi boiler, controller
Enters the performance data view so you can scroll through the data numbers listed in the performance data table.
- Press and hold the Down button, then press and hold the Domestic Hot Water button at the same time.
- Press and hold the Down button for two seconds.
- Use the Up and Down buttons to scroll to the data number you need.
- The value for the selected data number shows automatically on the display.
- To exit, hold the Down button and press and hold the Domestic Hot Water button together.
Access to emissions test switches
Viessmann · Vitocrossal 300 CA3B, all sizes 2.5 to 6.0
Emissions test switches D, E and F are behind the boiler front panels on multi-section boilers.
- Open the front top and bottom boiler panels and the control covers.
- Use switches D, E and F for the emissions test.
Activate the filling and venting program
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Starts the venting (bleeding) program in service functions. The burner stays off while the circulation pump cycles.
- Press OK and the menu button together for about 4 seconds.
- Select Service functions.
- Select Filling.
- Press OK or the back button to end the filling function when done.
Actuator test access
Viessmann · Vitotronic 300 GW6B
Opens the actuator test to switch individual outputs on or off for testing.
- From the home screen tap Menu.
- Tap Service.
- Enter the viservice password.
- Tap Actuator test.
Actuator test for low and high fire
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Used during combustion checks to hold the burner at low or high fire.
- Open the service menu by pressing OK and the key shown in the manual at the same time for about 4 seconds, then select Actuator test.
- Select Base load OFF to run low fire.
- Select 'all actuators off' to end the test.
- Select Full load OFF to run high fire.
- Press the exit key to leave the actuator test.
Actuator test for low fire and high fire combustion check
Viessmann · Vitodens 200-W B2HA
Use the Service menu actuator test to hold the burner at low fire or high fire for combustion checks. The key combination symbols are missing in the source text.
- Connect a flue gas analyzer to the test port on the vent pipe adaptor.
- Open the gas shut-off valve, start the boiler and create a heat demand.
- Open the Service menu by pressing OK and the key shown (symbol not legible) together for about 4 seconds.
- Select Actuator test.
- For low fire, select Base load OFF so Base load ON appears, then measure CO2 and O2.
- For high fire, select Full load OFF so Full load ON appears, then measure CO2 and O2.
- Select all actuators off to end the test, and record values in the Maintenance Record.
Actuator test of outputs
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Each output can be switched on or off individually. All actuators are switched off before a new one is selected. Only outputs that match the installed equipment and control unit configuration (lead or service control) will respond.
- From the home screen tap Service and enter the viservice password.
- Select Actuator test.
- Select the output to test, for example DHW tank primary pump, Htg circ pump HC2, Mixing valve HC3 or Solar circuit pump.
- Check that the actuator responds as listed in the actuator table.
Actuator test on the boiler group
Viessmann · Vitodens 100-W
Runs the actuator test for the Boiler group from the service menu.
- Open the service menu (see the button combination tip).
- Select Actuator test and press OK.
- Select the Boiler group and press OK.
Actuator test overview
Viessmann · Vitocrossal 200 CI2 with the relevant equipment level
The actuator test lets you switch individual outputs on and off from the service menu. Which outputs are available depends on the system equipment level. Groups: gas condensing boiler (burner modulation, minimum and maximum output, burner 1 and 2 where fitted, ventilation air supply, hydraulic shut-off valve), heating group (primary circuit pump speeds and on/off, mixer open/stop/close for HC2 and HC3 and the second HC3 entry as printed, heating zone pumps 1 to 3, circulation pump speed in %, heating circuit pump speeds), and DHW group (circulation pump, DHW tank heating, DHW recirculation pump).
- Enter the service menu (see access tip) and open the actuator test.
- Select the output group and the function to test, such as "Minimum heating output" or a pump On/Off.
- For mixers, use Open, Stop or Close and check the valve moves as expected.
Actuator test: drive fan, burner, pump and 3-way valve by hand
Viessmann · Vitodens 200-W B2HE 85, 120, 150, 199
Each actuator test function runs for 30 s: fan rpm, burner Off / Min / Max heating / Max DHW, 3-way valve Heating / Centre / DHW, pump speeds, mixers, zone pumps.
- Service menu > Actuator test
- Pick the group (Boiler, Heating, DHW, Solar) and the function
- Function stays active 30 s, then drops out
Adjust CO2 at full load
Viessmann · Vitocrossal 300 CA3B Dual Fuel burner
Adjusts the CO2 level at upper heating input.
- Set the service display to 100 (100%) for upper heating input.
- Check the CO2 level at the flue pipe.
- If the CO2 is out of range, remove cap B and turn adjusting screw A in small steps with a 3 mm Allen key.
- Turning clockwise lowers CO2 (less gas). Turning counter-clockwise raises CO2 (more gas).
- Record the reading in the maintenance report on page 158.
Adjust CO2 at partial load
Viessmann · Vitocrossal 300 CA3B Dual Fuel burner
Adjusts the CO2 level at lower heating output and returns the boiler to operating mode.
- Press the button until the service indicator shows 0 (lower heating output).
- Measure CO2 at the flue gas pipe.
- If needed, unscrew cover cap B and turn adjustment screw A in small steps with a Torx 40 driver. Clockwise increases CO2; counter-clockwise decreases CO2.
- Record the reading in the maintenance record on page 158.
- Start the upper and lower heating outputs again via the burner control unit and recheck.
- Press the two buttons together for more than 2 seconds to return the burner to operating mode.
Bleeding air program
Viessmann · Vitodens 200-W B2HA 80 to 100
Bleeds air from the system. The pump cycles the same way as the venting program and the burner is off.
- Activate the program as described in the Venting the heating system section.
- The pump runs alternately on and off for 30 seconds each over 20 minutes.
- Burner remains off during the program.
Brief scan
Viessmann · Vitodens 200-W B2HA 112/150/399/530
The brief scan shows temperatures, software versions and connected components on 9 lines with 6 fields each.
- Press OK and the second key together for about 4 seconds.
- Select 'Diagnosis', then 'Brief scan'.
- Press OK to view the 9-line display.
Brief scan (Vitotronic 200)
Viessmann · Vitotronic 200
The brief scan shows temperatures, software versions and connected components in 4 lines with 6 fields each. The field-by-field table on the source page is partly garbled in this copy, so check the original page for exact field meanings.
- Press OK and the second button until the control is in service mode.
- Select Diagnosis.
- Select Brief scan.
- Press OK.
- Read the 4 lines of values.
Brief scan (Vitotronic 300-K)
Viessmann · Vitotronic 300-K
The brief scan shows 9 lines with 6 fields each: system type, software versions, KM BUS participants, LON addresses and connected remote controls per heating circuit. The field table is partly unreadable in this copy.
- Press OK and the second button until the control is in service mode.
- Select Diagnosis.
- Select Brief scan.
- Press OK.
- Read the 9 lines; check the remote control entries for each heating circuit.
Brief scan of boiler values
Viessmann · Vitodens 200-W and Vitocrossal 300 CU3A with Vitotronic 200
Brief scan shows 9 lines of 6 fields with setpoint and actual boiler temperature, software versions, burner control unit type, flow sensing state and LON/KM BUS details. Field meanings are given per line in the manual table; read the manual for the exact line and field layout.
- Enter the service level.
- Select "Diagnosis", then "Brief scan".
- Tap OK to show the 9-line display and page through the brief scan entries.
Brief scan of operating data
Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352
Shows temperatures, software versions and connected components on 9 lines with 6 fields each. A sensor that is faulty shows "- - -" on the display.
- Enter the service level.
- Select "Diagnosis", then "Brief scan".
- Press OK. The display shows 9 lines with 6 fields each.
Brief scan of system data
Viessmann · Vitotronic 200-H HK1B
The brief scan shows temperatures, software versions, connected components and LON/KM BUS counts over 9 lines of 6 fields each. The field layout in the manual is hard to read in this extract, so check the printed table for exact field meanings. Fields 3 and 5 show the same values.
- Press OK together with the second button for about 4 seconds.
- Select 'Diagnosis', then 'Brief scan'.
- Press OK to view the 9 lines of fields.
Brief scan of system information
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
The brief scan gives an overview of system schemes, control unit and extension software versions, remote control type, KM BUS participants, LON address and communication module versions.
- From the home screen tap Service and enter the viservice password.
- Select Diagnosis, then Brief scan.
- Read the required line in the overview table (11 lines, 6 fields).
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.