Viessmann Boiler: Actuator test of outputs
Actuator test of outputs on a Viessmann boiler: Each output can be switched on or off individually. All actuators are switched off before a new one is selected. Only outputs that match the installed equipment and control unit configuration (lead or service control) will respond.
Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0
How to fix actuator test of outputs: step by step
- From the home screen tap Service and enter the viservice password.
- Select Actuator test.
- Select the output to test, for example DHW tank primary pump, Htg circ pump HC2, Mixing valve HC3 or Solar circuit pump.
- Check that the actuator responds as listed in the actuator table.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
More service & test modes tips for boiler
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 119. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.