Viessmann Boiler: Actuator test for low fire and high fire combustion check
Actuator test for low fire and high fire combustion check on a Viessmann boiler: Use the Service menu actuator test to hold the burner at low fire or high fire for combustion checks. The key combination symbols are missing in the source text.
Applies to: Vitodens 200-W B2HA
How to fix actuator test for low fire and high fire combustion check: step by step
- Connect a flue gas analyzer to the test port on the vent pipe adaptor.
- Open the gas shut-off valve, start the boiler and create a heat demand.
- Open the Service menu by pressing OK and the key shown (symbol not legible) together for about 4 seconds.
- Select Actuator test.
- For low fire, select Base load OFF so Base load ON appears, then measure CO2 and O2.
- For high fire, select Full load OFF so Full load ON appears, then measure CO2 and O2.
- Select all actuators off to end the test, and record values in the Maintenance Record.
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.