Viessmann Air Handler: ALARM contact (CN33) for external alarm
ALARM contact (CN33) for external alarm on a Viessmann air handler: Dry normally open output that closes when the unit has a fault, which triggers the external alarm or annunciator. The unit supplies no voltage, so the alarm system must provide power. Rated 250 VAC, 10 A maximum.
Applies to: Main board CN33 ALARM terminal
How to fix alarm contact (cn33) for external alarm: step by step
- Wire the alarm interface or annunciator to CN33 with its own power source.
- Keep the load within 250 VAC and 10 A.
If the unit shows an error code, look it up: Viessmann Air Handler codes
Models
DLFLABH36XA3DLFLABH48XA3DLFLABH60XA3DLFSABH18XB3DLFSABH24XB3DLFSABH30XB3DLFSABH36XB3DLFUAAQ18XB3DLFUAAQ24XB3DLFUAAQ30XB3DLFUAAQ36XA3DLFUAAQ36XB3DLFUAAQ48XA3DLFUAAQ60XA3
More other tips for air handler
Source: DLFSAB and DLFLAB Service Manual, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.