Other: Air Handler tips (part 5 of 6)
Short, practical technician tips on other for air handler. Check each one against the manual for your exact model before acting.
Remote condensate overflow switch
Carrier · All D5FUHA units with a field overflow switch
The unit accepts a field-supplied condensate overflow switch. When it is used, the overflow device must open its contact during an overflow so the unit switches off.
- Remove jumper J1.
- Connect the installer-supplied condensate overflow device to CN5 as shown in the wiring figure.
- Check that the device opens its contact during an overflow condition so the system turns off.
Remote control range and placement
Carrier · Wireless remote
The remote works up to about 26 ft (8 m) with no obstructions. Point it toward the right side of the indoor unit when sending commands. With the timer in use, keep the remote within about 26 ft of the fan coil.
- Point the remote at the right side of the indoor unit.
- Keep the remote within 26 ft (8 m) with no obstructions.
- Keep the remote within this range when timer functions are used.
Remote fault alarm output (CN33)
Carrier · D5FUHA with alarm output used
CN33 is a dry (passive) output and does not supply voltage itself, so the installer must provide a voltage signal. The relay is normally open during normal operation and closes when a fault is active.
- Wire the alarm device to CN33 and supply the required voltage from the installer side.
- Confirm the device reacts when a fault closes the relay.
Replace the control board fuse
Carrier · D5FULA control board
The control board has an overcurrent fuse with its rating printed on the board. Only a blast-proof ceramic fuse of the identical rating may be used.
- Turn off the unit and disconnect power.
- Read the fuse rating printed on the control board.
- Replace it only with an identical blast-proof ceramic fuse.
Replacement of control board fuse
Carrier · Indoor and outdoor control boards with fuse
The control board has an overcurrent fuse. The fuse rating is printed on the board, for example T3.15AL/250VAC, T5AL/250VAC, T5A/250VAC or T10A/250VAC.
- Read the fuse rating printed on the circuit board before replacing it.
- Use only a blast-proof ceramic fuse.
- Replace the fuse only with an identical component.
Replacing the circuit board fuse
Carrier · Indoor and outdoor PCB overcurrent fuse
Only a blast-proof ceramic fuse may be used. Match the rating printed on the circuit board.
- Check the fuse rating printed on the circuit board.
- Replace with an identical blast-proof ceramic fuse.
Return air and plenum sealing
Carrier · All installations with return air plenum
There must be an airtight seal between the bottom of the air handler and the return air plenum. Return air must not be drawn from a room with a gas appliance, water heater or carbon monoxide-producing device such as a wood fireplace.
- Seal the plenum-to-cabinet joint with fiberglass sealing strips, foil duct tape, caulking or an equal method.
- Confirm return air is not drawn from a room that contains a gas or CO-producing appliance.
- Apply sealant where wires, refrigerant pipes and condensate pipes enter the cabinet.
- Seal drain line holes with duct tape or flexible sealant so warm air cannot enter.
Save energy with timers, closed doors and clear airflow
Carrier · All D5FUH crossover air handler sizes
Keep doors and windows closed, use the timer functions to limit run time, keep air inlets and outlets clear, and check the filter regularly.
- Keep doors and windows closed while cooling or heating.
- Use TIMER ON and TIMER OFF to limit run time.
- Do not block the air inlet or outlet and do not place objects near them.
- Inspect and clean the air filter regularly.
Seal cabinet penetrations
Carrier · Indoor cabinet
Warm air must not enter through gaps around wires, refrigerant pipes, condensate pipes or drain lines.
- Apply sealant around wires, refrigerant pipes and condensate pipes where they enter the cabinet.
- Seal around drain line holes with duct tape or flexible sealant.
Sealed and intrinsically safe components
Carrier · Electrical and sealed component repair
Sealed electrical components and intrinsically safe components must be replaced with parts specified by the manufacturer. Check that cabling is not worn, corroded, pinched, vibrating or sharp-edged. Only use manufacturer-approved parts.
- Replace sealed or intrinsically safe components only with manufacturer-specified parts.
- Inspect cabling for wear, corrosion, pressure, vibration and sharp edges.
- Use only manufacturer-approved replacement parts.
Secondary drain pan over finished space
Carrier · D5FSAA / D5FLAA air handler
A field-built secondary drain pan with a drain line to the outside is required over a finished living space or any area that overflow could damage. Some local codes require one for any horizontal install.
- Install a field-built secondary drain pan with a drain pipe to the outside where overflow could cause damage.
- Check local code for horizontal installs.
Sleep function behaviour
Carrier · D5FSAA
Sleep is available in cooling, heating, auto or heat pump plus electric heater modes. In cooling the set point rises 1.8°F (1°C) each hour up to 86°F (30°C), then holds after 2 hours with the indoor fan at low. In heating the set point drops 1.8°F (1°C) each hour down to 60.8°F (16°C), then holds after 2 hours with the fan at low. Anti-cold wind takes priority in heating.
- Select sleep with the remote and confirm the mode is cooling, heating, auto or heat pump plus electric heater.
- Expect the set point to step by 1.8°F (1°C) per hour for 2 hours, then hold.
- In auto mode, after 1 hour the set point moves 1.8°F (1°C) up for cooling or down for heating; in fan mode it does not change.
Technician qualification for refrigerant work
Carrier · D5FULA crossover evaporator coil with flammable refrigerant
Anyone working on or opening a refrigerant circuit must hold a current certificate from an accredited assessment authority for safe refrigerant handling. Maintenance needing other skilled staff must be supervised by a competent person.
Three-minute protection
Carrier · D5FS(L)AAH
The unit will not restart for about 3 minutes after running and being restarted immediately.
Timer function (24-hour relative timer)
Carrier · D5FSAA with wired or wireless remote
The timer covers 24 hours and uses relative time, not clock time. It can be set as Timer On, Timer Off, Timer On/Off or Timer Off/On. The timer does not change the running mode. If the unit is off when a timer-off is set, it stays off until the set time is reached.
- Select the timer type you need: On, Off, On/Off or Off/On.
- Set the time; it counts from the moment it is set, not from the clock.
- Expect the timer LED to switch off when the set time is reached, with the running mode unchanged.
Transport, marking and storage of flammable refrigerant units
Carrier · Units with flammable refrigerant
Handling rules for units with flammable refrigerant.
- Follow transport rules for flammable gas equipment; the number of units that can ship together is set by those rules.
- Follow local rules for signs and safety labels in work areas.
- Store the unit according to the strictest applicable rule.
- Make sure packed units are protected so damage cannot cause a refrigerant leak.
Troubleshooting after failed test run
Carrier · D5FULA test run
If the unit malfunctions or does not run as expected during the test, consult the Troubleshooting section of the Service Manual before contacting customer service.
- Refer to the Service Manual Troubleshooting section before calling customer service.
Unit element abbreviations
Carrier · D5FSAA
Reference list of the abbreviations used for temperatures and setpoints.
- T1: indoor room temperature.
- T2: evaporator coil temperature.
- T3: condenser coil temperature.
- T4: outdoor ambient temperature.
- TP: compressor discharge temperature.
- TS: setting temperature.
- Tsc: adjusted setting temperature.
Unit selection for sensible loads
Carrier · DLFULA evaporator coil
Select equipment that matches or slightly exceeds the anticipated peak load. For high sensible load spaces, base the selection on sensible load and adjust for room wet bulb temperature so the equipment is not undersized.
- Match or slightly exceed the peak load.
- For high sensible load spaces, size on sensible load and adjust for room wet bulb temperature.
Use only approved parts and accessories
Carrier · D5FULA crossover evaporator coil, sizes 24K - 60K
Only the accessories and replacement parts specified by the manufacturer may be used. Non-approved parts can cause leaks, shock, fire and failure, and can void the warranty.
UV, fresh air or ion generator on the WORK output
Carrier · D5FUHA with UV, fresh air or ion accessory
The WORK output follows the fan. The accessory only runs while the fan runs.
- Wire the UV lamp, fresh air damper or ion generator to the WORK output as shown in the accessory wiring figure.
Wire and line routing
Carrier · D5FUAA field wiring with line set
Keep control wiring separate from refrigerant piping.
- Bundle power cable, signal cable and piping with binding tape only after the copper pipes are connected to the outdoor unit.
- Do not intertwine or cross the signal cable with other wiring.
Wired controller options and limits
Carrier · D5FUAA with KSACN1401AAA or KSACN1701BAA wired controller
KSACN1401AAA and KSACN1701BAA wired controllers are sold separately. The wired controller and a 24 V thermostat cannot be used at the same time. Do not connect power to the communication line; this can damage the system.
- Refer to the wiring template for the chosen controller's wiring method.
- Do not run the 24 V thermostat and the wired controller together.
- Do not connect line power to the communication line.
Wiring order and separation
Carrier · D5FUHA system wiring
Connect outdoor wires before indoor wires. Keep power and signal wiring separated and do not cross them.
- Connect the outdoor unit wires first, then the indoor wires.
- Keep power supply leads away from communication leads.
- Use strain relief and clamp cables so they do not pull on the terminals.
- Insulate any unused wires with electrical tape.
Wiring precautions before connecting power
Carrier · D5FULA
Key electrical rules from the wiring section. Power to the unit must be off before any wiring.
- Turn off main power and lock out the disconnect before any wiring work.
- Connect the outdoor unit wires before the indoor wires.
- Use copper wire only and keep power leads separate from communication leads.
- Keep power supply within 90-110% of rated voltage.
- Use a branch circuit dedicated to this unit; do not share the outlet.
- Use a disconnect or breaker with at least 1/8 in (3 mm) contact separation on all poles.
- Ground the unit properly and tighten every connection.
- Keep wires away from refrigerant tubing, compressor and moving parts.
- Do not cross power wiring with signal wiring.
- Wait 10 minutes after power-off before touching electrical components.
- Do not connect 24 VAC to S1-S2; this will damage the system.
Thermostat and flow switch cable connections
Navien · H2Air thermostat and flow switch inputs
Thermostat wiring or connectors go into the H2Air contacts. Flow switch fork connectors go into their contacts.
- Insert the thermostat wiring or connector into its contact.
- Tighten the terminal screw with a screwdriver.
- Insert the flow switch fork connectors into the flow switch contact.
- Tighten the terminal screw with a screwdriver.
Wiring a heating/cooling combo system
Navien · Heating/cooling combo systems using an AHU
For cooling, the thermostat cooling call goes to the AHU cooling input and the thermostat R goes to the AHU R output.
- Connect the thermostat Y terminal to the AHU cooling input Y.
- Connect the thermostat R terminal to the AHU R output.
ALARM contact (CN33) for external alarm
Viessmann · Main board CN33 ALARM terminal
Dry normally open output that closes when the unit has a fault, which triggers the external alarm or annunciator. The unit supplies no voltage, so the alarm system must provide power. Rated 250 VAC, 10 A maximum.
- Wire the alarm interface or annunciator to CN33 with its own power source.
- Keep the load within 250 VAC and 10 A.
Built-in control functions (guide spec)
Viessmann · Indoor ducted units, DLFSDA and DLFLDA
Indoor ducted units include automatic restart after power failure at the prior operating conditions, a 24-hour timer for auto start/stop, return air temperature sensing, indoor coil freeze protection, high temperature protection in heat pump mode, dehumidification mode, fan-only operation, user-selectable fan speed or automatic fan, and automatic heating-to-cooling changeover with deadband. Error messages appear on the unit.
Built-in indoor unit control functions
Viessmann · Indoor ducted fan coil units
The indoor unit has automatic restart after power loss, a 24-hour timer for auto start/stop, return-air temperature sensing, indoor coil freeze protection, and wireless infrared remote control. In heat pump mode it also has indoor coil high-temperature protection and a deadband to prevent rapid heating/cooling changeover. Dehumidification and fan-only modes are included. Diagnostics show error messages on the unit.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.