Trane Furnace: Wall vent clearances and shielding
Wall vent clearances and shielding on a Trane furnace: Clearances depend on wall construction and vent material. Combustible walls need an air space and a shield, and wall-vent flue gas can damage nearby materials.
Applies to: Horizontal wall venting
How to fix wall vent clearances and shielding: step by step
- Use 0 in clearance to combustible walls for PVC vent pipe.
- Use 1 in clearance to combustible walls for Type 29-4C stainless vent pipe.
- Hold a 1 in air space at combustible walls where the wall pipe passes through, and set the approved termination in place.
- Seal noncombustible wall penetrations with cement mortar inside and outside, with the hole sized to keep pitch and seal properly.
- Where flue gas could damage the wall, install a corrosion-resistant shield, at least 24 gauge stainless or aluminized, minimum 12 in x 12 in, fastened to both the inside and outside of the wall.
- Silicone-caulk all cracks, seams and joints within 3 ft of the vent terminal.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane installer's guide, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.