Trane Furnace: Vent and inlet terminal spacing
Vent and inlet terminal spacing on a Trane furnace: Terminal spacing for the vent and inlet is given in the venting figures. The numbers for each dimension depend on which termination you are building, and the reference point for each one should be confirmed against the manual drawing before you cut pipe. What I usually find going wrong is people mixing dimensions from different termination styles. Pipe supports and insulation also matter here, since a sagging or frozen pipe will cause a pressure switch trip the first time it gets cold.
Applies to: Two-pipe (direct) venting
Common causes of vent and inlet terminal spacing
- Exhaust and inlet ends too close, recirculating flue gas into the intake
- Dimensions mixed up between different termination styles
- Pipe unsupported, sagging and collecting condensate
- Fitting in an unheated space left uninsulated and freezing up
How to fix vent and inlet terminal spacing: step by step
- Keep at least 9 in between the end of the exhaust pipe and the end of the inlet pipe.
- Check the 6 in minimum and 24 in maximum dimension (and the 12 in minimum and 15 in maximum dimension) against the drawing for the specific termination.
- Support vent and inlet pipe at no more than 3 ft intervals.
- Insulate any fitting that passes through an unheated space.
- Look at the terminals after install to confirm nothing blocks them.
- Run a heating cycle and confirm the pressure switch stays closed.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane installer's guide, p. 24, 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.