Trane Furnace: Twinning furnaces
Twinning furnaces on a Trane furnace: Twinned Trane furnaces share a duct system, so they have to be matched and see equal resistance. Before wiring anything, confirm both units are identical in configuration and size, and that the returns and ducts are balanced. Wire per the field wiring diagrams only.
Applies to: Twinned furnace installations
Common causes of twinning furnaces
- Furnaces of different configuration, capacity or airflow
- Unequal return pressure drops between the two furnaces
- Duct lengths and sizes not equivalent
How to fix twinning furnaces: step by step
- Confirm both furnaces have the same configuration, capacity and airflow.
- Use common returns with equal pressure drops, or ducts with equivalent lengths and sizes.
- Wire the furnaces per the field wiring diagrams for the hookup.
- Power down both units before working on the control wiring.
- After startup, compare temperature rise on each furnace.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane installer's guide, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.