Trane Furnace: Temporary heating during building construction
Temporary heating during building construction on a Trane furnace: I see it all the time, a builder wants the new furnace running while drywall dust is still flying. The manufacturer allows it only if every listed condition is met. Drywall dust, sanding dust and cold return air are what kill a heat exchanger and a blower in a few weeks, so the conditions are not optional. If you cannot meet them all, do not use the furnace as a construction heater.
Applies to: Furnaces used during construction
Common causes of temporary heating during building construction
- Venting not finished or not installed per the instructions
- Field jumpers on the thermostat or controls
- Return duct incomplete or unsealed, pulling in dust and cold air
- Combustion air coming from inside a dusty building
- Return air temperature below 55 or above 80 degrees F
How to fix temporary heating during building construction: step by step
- Make sure the venting system is complete and installed per the instructions.
- Control the furnace only with a room thermostat, with no field jumpers.
- Make sure the return air duct is complete, sealed to the furnace, and clean filters are installed.
- Verify input rate and temperature rise are within the nameplate values.
- Make sure 100% of combustion air comes from outside the structure.
- Keep return air temperature between 55 and 80 degrees F.
- After construction, clean the furnace, ducts and components and verify ignition, input, temperature rise and venting per the manufacturer's instructions.
- Replace filters before the homeowner takes over.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane AUH1B080A9421B installer's manual, p. 3 (Safety section item 9 and Caution note). Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.