Trane Furnace: PVC solvent cement joint procedure
PVC solvent cement joint procedure on a Trane furnace: Cure time varies with fit, temperature and humidity.
Applies to: PVC vent joints
How to fix pvc solvent cement joint procedure: step by step
- Cut pipe square, remove burrs, chamfer the pipe end, and clean the socket and pipe of dirt, grease, moisture and chips.
- Check fit, then wipe the socket and pipe with cleaner-primer. Coat the socket inside and the pipe outside. Do not let primer dry before cementing.
- Apply a thin coat of cement evenly in the socket. Quickly coat the pipe end heavily, then push it in with a slight twist until it bottoms out.
- Hold the pipe in the fitting for 30 seconds so the tapered socket does not push it out.
- Wipe excess cement from the joint with a rag. Allow 15 minutes before handling.
- Make sure all joints are watertight. Flue condensate is acidic and leaks can damage equipment.
- Use RTV sealant on the first joints from the furnace so they can be removed later without cutting. Support all joints properly.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane AUH1B080A9421B installer's manual, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.