Trane Furnace: Horizontal venting through a wall
Horizontal venting through a wall on a Trane furnace: Wall-vent terminations must sit clear of expected snow and must not sit where condensate or staining can cause trouble. Vent pipe must slope upward so condensate drains back to the furnace.
Applies to: Upflow and downflow furnaces in horizontal venting
How to fix horizontal venting through a wall: step by step
- Keep the vent and inlet terminals at least 12 in above the highest expected snow level or grade, whichever is higher.
- Keep the terminal away from public walkways, soffit vents, crawl space vents, and any spot where condensate or vapor can cause a nuisance or damage.
- Slope the vent upward at 1/4 in per foot so condensate runs back to the furnace.
- Support horizontal pipe at no more than 3 ft intervals, with the first support as close to the furnace as possible.
- Do not let the furnace, blower housing or inducer carry the weight of the flue pipe.
- Keep the elbow and tee as close together as possible.
- Do not route return air through the side of the cabinet on horizontal applications.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane installer's guide, p. 24-26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.