Trane Furnace: Horizontal vent termination through wall

Updated · by Aurora Star Tech Inc.

Horizontal vent termination through wall on a Trane furnace: On a horizontal wall termination, the thing I find wrong most often is a vent set too close to grade. Snow drifts, mulch or a flower bed will bury it and the furnace trips on the pressure switch in the first cold snap. Vent and inlet terminals must clear the expected snow level, and the dimensions in the figures are what the manufacturer tested, so use them.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Horizontal venting through wall

Common causes of horizontal vent termination through wall

  • Terminals too low and covered by snow or landscaping
  • Exhaust and inlet too close, recirculating flue gas
  • Insufficient overhang
  • Elbow and tee spaced too far apart, upsetting the termination dimensions
  • Wrong termination kit mixed with the figure dimensions

How to fix horizontal vent termination through wall: step by step

  1. Locate the vent and inlet terminals at least 12 in above the normally expected snow level.
  2. Maintain at least 12 in above the highest anticipated snow level or grade, whichever is higher.
  3. Use at least 12 in of overhang for the termination (per figure).
  4. Keep the exhaust and inlet ends separated by at least 9 in measured end to end (per figure).
  5. Keep the elbow and tee as close together as possible.
  6. Use 6 in minimum to 24 in maximum between the terminal and the adjacent fitting (per figure).
  7. Termination kits BAYVENT200B or BAYAIR30AVENTA can replace the terminal options shown in the figures.
  8. Walk around outside after install and check for obstructions.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Trane Furnace codes

Source: Trane AUH1B080A9421B installer's manual, p. 24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.