Trane Furnace: High altitude derate and orifice change
High altitude derate and orifice change on a Trane furnace: Input is based on sea level and is only changed above 2,000 ft.
Applies to: Installations at 2,000 ft and above
How to fix high altitude derate and orifice change: step by step
- Up to 2,000 ft, do not change the input rating.
- At 2,000 ft or higher, reduce input 4% for each 1,000 ft above sea level.
- Check input by clocking gas flow and multiplying by the local heating value.
- Change input by manifold pressure first: upflow natural gas 3.0 to 3.7 in. W.C.; downflow natural gas 3.0 to 4.5 in. W.C.
- If the target input cannot be reached with pressure, change the orifices. LP installations always need an orifice change.
- Above 4,000 ft, a pressure switch change may be needed; use the BAYHALT high altitude accessory kit listed in product data.
- Recheck input rate and temperature rise after any orifice change.
- Install above 2,000 ft in line with local code, or the National Fuel Gas Code / CSA 149.1 and the listed high altitude conversion kit.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane 18-CD29D1-11 installer's guide, pp. 34, 35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.