Trane Furnace: Downward venting
Downward venting on a Trane furnace: Downward venting is when the vent has to go down before it goes out, usually through a basement wall or floor. It works, but it is limited in length, and because water naturally runs down the pipe you need a condensate trap on the vent so it does not run back into the furnace. Think of it like a kitchen sink trap. Slopes and supports are what keep the system working long term.
Applies to: Vertical/downward venting from a 40 in upflow or downflow furnace
Common causes of downward venting
- Downward run longer than allowed
- No condensate trap on the vent, so water runs to the furnace
- Horizontal pipes without slope holding water
- Trap drain not connected to a proper drain
- Termination too low or too high above the roof
How to fix downward venting: step by step
- Limit downward vent length to a maximum of 15 equivalent feet.
- Install a condensate trap of at least 6 in height on the vent pipe.
- Slope all horizontal pipes at 1/4 in per foot and support them at no more than 3 ft intervals.
- Connect the vent and inlet condensate trap to a condensate drain pump, an open or vented drain, or the outlet hose of the furnace condensate trap.
- Keep 12 in minimum clearance above the highest expected snow level, not exceeding 24 in above the roof.
- After startup, check that the trap holds water and drains freely.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane installer's guide, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.