Trane Furnace: Condensate drain for horizontal installations
Condensate drain for horizontal installations on a Trane furnace: Horizontal installs are left-side drain only, and the trap has to move outside the cabinet. Auxiliary drain pan goes under any horizontal evaporator or 95% furnace.
Applies to: Upflow and downflow horizontal installations
Common causes of condensate drain for horizontal installations
- Furnace being installed on its side
- Trap still inside the cabinet from the upflow setup
- Inducer hose on the wrong drain tap
- Drain connected to a closed line that backs up
- No auxiliary drain pan under the coil
How to fix condensate drain for horizontal installations: step by step
- Install an auxiliary drain pan under any horizontal evaporator or 95% furnace, connected to a separate drain line with no trap, because a trap would block the overflow.
- Move the trap to the outside of the cabinet through the long circular hole, next to the secondary cell.
- Trim the larger drain line from the secondary cell to fit to the new trap location.
- On upflow units, plug the blower deck hole the tube went through and extend the inducer drain tube with the supplied tubing if needed.
- Move the inducer hose to the other drain tap, 90 degrees clockwise, and move the cap to the unused tap.
- Connect drains only to an open or vented drain.
- Pour water into the trap and confirm it drains with no leaks.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane installer's guide, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.