Trane Furnace: Combustion and input check
Combustion and input check on a Trane furnace: Combustion and input check means finding out how much gas the furnace is actually burning. You do it by timing the gas meter with only the furnace running, then converting to input and comparing to the nameplate. It sounds fiddly but it is simple arithmetic, and it tells you quickly if the unit is over or underfired. Overfiring shortens heat exchanger life and can create unsafe combustion.
Applies to: All UH1 and DH1 furnaces
Common causes of combustion and input check
- Gas input above the nameplate rating
- Other gas appliances left on during the test
- Dial size misread or wrong conversion
- Wrong orifices or high manifold pressure
- Utility heating value assumed instead of read from the bill
How to fix combustion and input check: step by step
- Make sure all other gas appliances are off, including pilots.
- With the furnace running, clock the gas meter for one revolution and note the dial size.
- Find the clocked seconds in the flow table and read the cfh on the same row.
- Adjust the reading for dial size: a 1 cu ft dial divide by 2; a 1/2 cu ft dial divide by 4; a 5 cu ft dial multiply by 10 and divide by 4.
- Multiply the result by the gas heating value from the utility and compare to the nameplate. It must not exceed the nameplate rating.
- If input is too high, check manifold pressure and orifice size. Gas adjustments are for a licensed technician.
- Relight other appliances when done.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane 18-CD29D1-11 installer's guide, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.