Trane Furnace: Airflow and temperature rise check
Airflow and temperature rise check on a Trane furnace: At startup on this Trane, confirm airflow by checking inlet and outlet air temperatures against the furnace rating plate. Do it with the furnace stabilized and the panels in place, because open panels give false readings. Never change a motor speed without first disconnecting power.
Applies to: Airflow adjustment at startup
Common causes of airflow and temperature rise check
- Temperature rise outside the nameplate range because of blower speed
- Dirty filter or restricted ductwork reducing airflow
- Readings taken before the furnace stabilized
How to fix airflow and temperature rise check: step by step
- Run the furnace until temperatures stabilize with all panels closed.
- Check inlet and outlet air temperatures against the ranges on the furnace rating nameplate.
- If airflow must change, turn off power and use the wiring diagram to change the blower motor speed.
- Recheck the temperature rise after the change.
- Check the filter and registers if the rise stays out of range.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane 18-CD29D1-11 installer's guide, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.