Trane Furnace: Airflow adjustment check
Airflow adjustment check on a Trane furnace: Before changing airflow on an AUH1B furnace, check the air temperatures across the heat exchanger first. Airflow is changed at the blower motor speed taps, not in the control panel. Disconnect power before opening the blower door for any work. The blower door switch cuts power to the blower and gas valve when the door is removed, so keep all panels closed while you are measuring and do not defeat that switch.
Applies to: AUH1B furnaces
Common causes of airflow adjustment check
- Temperature rise outside the nameplate range
- Blower speed set wrong for the duct system
- Dirty filter or restricted ducts making it look like a blower speed issue
- Panels open or door switch not engaging
How to fix airflow adjustment check: step by step
- Measure inlet and outlet air temperatures with the furnace running steady, with panels closed.
- Confirm both are within the ranges printed on the rating nameplate.
- Before changing speed, check the filter and registers, because restriction is the usual cause.
- If airflow must change, use the wiring diagram to find the blower motor speed change.
- Disconnect power before opening the blower door for any work.
- Keep all panels closed during operation; the blower door switch cuts power to the blower and gas valve when the door is removed.
- Recheck temperature rise after any change.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane installer's manual (AUH1B040A9241A), p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.