Trane Furnace: Adjust gas valve manifold pressure
Adjust gas valve manifold pressure on a Trane furnace: Set manifold pressure with a gauge on the White-Rodgers 36G or 36J valve.
Applies to: White-Rodgers 36G and 36J gas valves
How to fix adjust gas valve manifold pressure: step by step
- Turn off all electrical power to the system.
- Attach a manifold pressure gauge with flexible tubing to the outlet pressure boss marked OUT P.
- Loosen the pressure tap test set screw one turn with a 3/32 in. hex wrench. Do not remove it.
- Turn on power and energize the valve.
- Remove the regulator cover screw. Turn the adjust screw clockwise to raise pressure or counterclockwise to lower it, until the gauge matches the value in the manifold pressure table.
- Replace and tighten the regulator cover screw.
- Cycle the valve several times and recheck the setting; repeat if needed.
- Turn off power, remove the gauge and tubing, and tighten the pressure tap screw.
- Leak check the outlet boss and pressure tap screw with soap solution.
- Turn on power and check unit operation.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane 18-CD29D1-11 installer's guide, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.