Rinnai Tankless Water Heater: CXP rack (TRW02CXP / TRW03CXP): recirculation set-up and slow hot water
CXP rack (TRW02CXP / TRW03CXP): recirculation set-up and slow hot water on a Rinnai tankless water heater: CXP199 units have a built-in pump (Smart-Circ). The rack needs either a dedicated return line or a thermal bypass valve at the far fixture, and the parameters must match.
Applies to: Rinnai TRW02CXP and TRW03CXP racks (CXP199)
Common causes of cxp rack (trw02cxp / trw03cxp): recirculation set-up and slow hot water
- Parameter 04 not matching the piping
- Loop too long
- MC-195T-US and Control-R Wi-Fi module both installed
- Used with hydronic heating
How to fix cxp rack (trw02cxp / trw03cxp): recirculation set-up and slow hot water: step by step
- Dedicated return line: set parameter 04 to dedicated mode (04b). No return line: fit a thermal bypass valve at the far fixture and set 04C (crossover).
- Loop limit: 400 ft with 3/4 in. pipe or 100 ft with 1/2 in. pipe, counting elbows.
- Parameter 05 sets pump cycling: 05A Economy (default), 05b Comfort (runs more), 05C Commercial (runs on and off all the time, more wear).
- Do not install the MC-195T-US timer and the Control-R Wi-Fi module together.
- Do not use these racks with hydronic heating.
- Insulate the hot and return lines.
If the unit shows an error code, look it up: Rinnai Tankless Water Heater codes
Models
CX160iCX199iCXP160iCXP199iRX130iRX160iRX180iRX199iRXP160iRXP199i
Source: Rinnai TRS with SENSEI CX Installation Instructions (100000870), 11 Configuring TRW02CXP and TRW03CXP Rack Models p.31-36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.