Rinnai Tankless Water Heater: BMS Gateway: reset IP address and admin password to default
BMS Gateway: reset IP address and admin password to default on a Rinnai tankless water heater: Puts the gateway back to IP 192.168.1.151, subnet 255.255.255.0, default gateway 192.168.1.254, admin password admin.
Applies to: Rinnai BMS Gateway with up to 6 commercial condensing tankless units (SENSEI CU160/CU199, CX160/CX199 or KB C199; do not mix KB and SENSEI on one gateway)
Common causes of bms gateway: reset ip address and admin password to default
- Forgotten password or IP
How to fix bms gateway: reset ip address and admin password to default: step by step
- Turn off power before opening the enclosure or unplugging connectors. The reset is done with the cover off, so work carefully around the board.
- Take off the six plastic screws and remove the front cover.
- Find the router inside the enclosure.
- Press and hold its IP Reset button. When the LED stops blinking and goes off, let go.
- Power cycle the gateway.
- Refit the cover.
- Touch screen passcode (separate from the web login) is 0151 by default, set on the Screens Setup tab.
If the unit shows an error code, look it up: Rinnai Tankless Water Heater codes
Source: Rinnai BMS Gateway Installation and Operation Manual (R-BMS-100 / RBMS100E / R-BMS-101, 2025), 10.2 Reset IP Address and Password to Default p.54; 7.2 p.43. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.