Updated · by Aurora Star Tech Inc.

Wire the condensate pump safety switch on a Rinnai boiler: Wires the pump's normally open contacts into the boiler so the boiler shuts down if the pump fails. Wiring must follow local codes and NEC.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: I-Series Plus condensing combi boilers with a condensate pump

How to fix wire the condensate pump safety switch: step by step

  1. Disconnect power to the boiler.
  2. Open the boiler cover and find the two white wires marked To Condensate Pump. They may sit behind the PC board.
  3. Cut off the crimp connectors and strip both wire ends.
  4. Use wire rated 18 AWG or larger, strip both ends, and connect with wire nuts or approved connectors to the normally open contacts on the pump.
  5. Reconnect power and press the On/Off button on the controller.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rinnai Boiler codes

Source: Rinnai I-Series Plus IP060160C installation manual, p. 65. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.