Rinnai Boiler: Venting slope and pressure plane rules
Venting slope and pressure plane rules on a Rinnai boiler: Slope rules for horizontal venting and rules against mixing vent pressure planes or sharing pipes.
Applies to: Horizontal and multi-pipe venting
Common causes of venting slope and pressure plane rules
- Venting in different pressure planes can cause poor boiler performance.
How to fix venting slope and pressure plane rules: step by step
- Do not install the boiler with venting in different pressure planes.
- Slope horizontal exhaust 1/4 in per foot (about 2 cm per metre) toward the boiler.
- Do not slope the combustion air pipe toward the boiler.
- Do not bring exhaust and combustion air together into a single PVC pipe with a fitting.
- Do not common-vent with another manufacturer's induced draft appliance.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.