Rinnai Boiler: Vent termination near an openable window or door (Canada, TB-200)
Vent termination near an openable window or door (Canada, TB-200) on a Rinnai boiler: Rinnai bulletin TB-200 (10/2024) changed Reference B in the I-Series Plus termination clearance tables for Canadian installs to match CSA B149.1. Older printed manuals show the old value.
Applies to: I-Series Plus combi IP060160C to IP199199C and heat-only IP060S to IP199S, Canadian installations
Common causes of vent termination near an openable window or door (canada, tb-200)
- Termination placed using the old Reference B value
- Inspector flags clearance to an openable window or door
How to fix vent termination near an openable window or door (canada, tb-200): step by step
- Applies to direct vent (concentric and twin pipe, Table 15 Ref. B) and room-air / non-direct vent (Table 23 Ref. B) terminations.
- Clearance from the termination to a window or door that can be opened, Canada:
- Input up to 10,000 Btu/h: 6 in. (15 cm).
- Over 10,000 up to 100,000 Btu/h: 12 in. (30 cm).
- Over 100,000 Btu/h: 36 in. (91 cm).
- Use the boiler's rated input from the rating plate to pick the line. Move the termination if it is too close.
- The same bulletin softens the maintenance warning wording (annual inspection is now 'recommended'); a licensed tech still does all repairs.
If the unit shows an error code, look it up: Rinnai Boiler codes
Models
I-Series Plus 150K and smaller
I-Series Plus 175K and higher
Source: Rinnai Technical Bulletin TB-200 (10/2024), I-Series Plus Boiler Manual Revisions for Termination Clearances and Maintenance Warning, p.1-2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.