Rinnai Boiler: Vent material and solvent rules

Updated · by Aurora Star Tech Inc.

Vent material and solvent rules on a Rinnai boiler: Exhaust piping must be solid core. Use the PVC or CPVC fitting, solvent and joining method given by the pipe manufacturer.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: PVC/CPVC venting

How to fix vent material and solvent rules: step by step

  1. Use solid core exhaust piping only.
  2. In Canada, thermoplastic vent pipe must be certified to ULC S636.
  3. Intake pipe may use any material listed in the approved materials table.
  4. Use PVC cement and primer that match the pipe material (PVC D2564, CPVC F493).
  5. Install 2 in vent screens (IPEX 196050) or 3 in vent screens (IPEX 196051) at the termination where the table calls for them.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rinnai Boiler codes

More commissioning tips for boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 36. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.