Twin pipe vent installation sequence on a Rinnai boiler: Connect the combustion air and exhaust pipes to the boiler using the supplied screws. Seal and seat each pipe properly.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Twin pipe venting

How to fix twin pipe vent installation sequence: step by step

  1. Remove and discard the screw from the combustion air vent connection.
  2. Remove and discard the combustion air vent cap.
  3. Install the combustion air vent pipe and make sure it is fully seated.
  4. Secure the combustion air vent pipe to the connection with the supplied screw.
  5. Install the exhaust vent pipe and make sure it is fully seated.
  6. Secure the exhaust vent pipe to the exhaust adapter ring with the supplied screw.
  7. Do not apply PVC glue, solvent or cleaner to the combustion air or exhaust gasket connections.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rinnai Boiler codes

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 41. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977