Rinnai Boiler: Simultaneous DHW and CH Is Not Functional (Combi Only)
Simultaneous DHW and CH Is Not Functional (Combi Only) on a Rinnai boiler: Boiler does not run DHW and CH at the same time.
Applies to: I-Series Plus combi boiler
Common causes of simultaneous dhw and ch is not functional (combi only)
- Parameter 08 off
- CH set point below 140°F/60°C (not allowed, including outdoor reset)
- DHW inlet temperature too hot
- DHW and CH heating loads beyond limits together
How to fix simultaneous dhw and ch is not functional (combi only): step by step
- Confirm parameter 08 is ON.
- Set the CH set point to 140°F/60°C or higher (outdoor reset settings included).
- Confirm the DHW inlet temperature is not too hot.
- Confirm the DHW and CH loads are within limits for simultaneous operation.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 117. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.