Rinnai Boiler: Room air vent piping configurations
Room air vent piping configurations on a Rinnai boiler: Approved room air venting uses 2 in or 3 in Schedule 40 PVC/CPVC or ABS, or 4 in B-vent pipe. Flexible venting (PP flex or Ubbink) is only approved for vertical non-direct vent room air installations; follow the flex vent manual. Do not install with venting in different pressure planes, as this can cause poor performance. Termination options include snorkel, side wall elbow or tee, upside-down U vertical, and vertical tee.
Applies to: Room air venting
Common causes of room air vent piping configurations
- Venting in different pressure planes causes poor boiler performance
How to fix room air vent piping configurations: step by step
- Select the termination configuration that suits the building (snorkel, side wall, upside-down U vertical, or vertical tee).
- Use 2 in or 3 in Schedule 40 PVC/CPVC or ABS, or 4 in B-vent, as the approved pipe.
- Slope the horizontal exhaust 1/4 in per foot back toward the boiler.
- Use Ubbink or PP flex only for vertical non-direct vent room air runs, and follow the flex vent manual.
- Do not mix venting that runs in different pressure planes.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation manual, p. 45. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.