Rinnai Boiler: Replacement gas valve assembly comes with a propane orifice
Replacement gas valve assembly comes with a propane orifice on a Rinnai boiler: Service gas control assembly 806000089 for the I-Series Plus 175K and larger ships with the propane (LP) orifice installed. On a natural gas unit the orifice must be swapped before firing.
Applies to: Rinnai I-Series Plus 175K BTU and larger boilers and combi boilers (gas valve assembly 806000089)
Common causes of replacement gas valve assembly comes with a propane orifice
- New gas valve assembly installed on a natural gas boiler without changing the orifice
How to fix replacement gas valve assembly comes with a propane orifice: step by step
- Gas off, power off. Gas work by a licensed gas technician only.
- Find the orifice cover plate on top of the gas valve and remove its 3 screws.
- Take out the LP orifice (gray) and put in the NG orifice (black) that comes in the box.
- Check the gasket: the grooved side must face outward. Refit the cover plate with the 3 screws.
- Leak test, then check combustion per the boiler manual.
- For other Rinnai products the service assembly is 106000117 (RU/CU tankless and the older I-Series boiler): NG orifice blue, LP orifice red.
If the unit shows an error code, look it up: Rinnai Boiler codes
Models
Source: Rinnai Gas Control Orifice Instructions U334-9053(01) / 800000266, p.1. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.