Rinnai Boiler: Pressure relief valve installation

Updated · by Aurora Star Tech Inc.

Pressure relief valve installation on a Rinnai boiler: The relief valve is required by ANSI Z21.13 and the ASME Boiler and Pressure Vessel Code. It must be accessible for service. An ASME 30 PSI valve is supplied with the boiler.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Relief valves on the CH and DHW circuits

How to fix pressure relief valve installation: step by step

  1. Fit the relief valve before any shut-off valve in the system.
  2. Make sure the valve meets ANSI Z21.22, CAN1-4.4 and/or ASME Section IV as applicable.
  3. Pipe the central heating relief valve for up to 30 PSI, rated for at least the boiler's maximum Btu/hr.
  4. Pipe the domestic hot water relief valve for up to 150 PSI, rated for at least the boiler's maximum Btu/hr.
  5. Pipe the discharge to the ground or a drain per local code. Keep the discharge line pitched downward and end it 6 in (152 mm) above a drain where discharge can be seen.
  6. Make the discharge end plain (unthreaded), at least 3/4 in nominal pipe diameter, and of material rated for water at 180°F (82°C) or higher.
  7. Do not plumb the relief valve into the condensate drain. Drain each one separately.
  8. Do not plug the relief valve, do not add reducers or restrictions to the relief line, and do not place any valve between the relief valve and the boiler.
  9. Protect the valve and discharge line from freezing.
  10. Manually operate the relief valve once a year to check that it works.
  11. If the valve discharges periodically, check for thermal expansion in the closed system and contact the water supplier or plumbing inspector. Do not plug the valve.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rinnai Boiler codes

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 59. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.