Rinnai Boiler: Massachusetts requirements for side wall horizontal gas venting
Massachusetts requirements for side wall horizontal gas venting on a Rinnai boiler: For gas models sold in Massachusetts with a side wall horizontal vent terminal less than 7 ft above finished grade, including over decks and porches. Only a properly trained licensed professional may install this direct-vent unit. Confirm these items are in place before the inspector signs off.
Applies to: Gas models sold in Massachusetts, side wall horizontal vent under 7 ft above grade
How to fix massachusetts requirements for side wall horizontal gas venting: step by step
- Confirm a hard-wired CO detector with alarm and battery back-up is installed on the floor level where the boiler is installed.
- Confirm a battery-operated or hard-wired CO detector with alarm is installed on each additional level served by the vent.
- If the boiler is in a crawl space or attic, the hard-wired detector with battery back-up may go on the next adjacent floor level.
- If the requirements cannot be met at completion, the owner has 30 days to comply. A battery-operated CO detector with alarm must be installed during that period.
- Use CO detectors that meet NFPA 720, are ANSI/UL 2034 listed and are IAS certified.
- Mount a metal or plastic sign on the building exterior at least 8 ft above grade, directly in line with the vent terminal. Lettering must be at least 1/2 inch high and read: "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS."
- Expect the state or local gas inspector to withhold approval unless the CO detectors and signage meet 248 CMR 5.08(2)(a)1 through 4.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation manual, p. 145. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.