Rinnai Boiler: Install concentric vent pipe and termination

Updated · by Aurora Star Tech Inc.

Install concentric vent pipe and termination on a Rinnai boiler: Concentric vent installation for the I-Series Plus. Follow the vent manufacturer's instructions and the termination diagrams in the manual.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Concentric 2 in x 4 in and 3 in x 5 in venting

How to fix install concentric vent pipe and termination: step by step

  1. Remove and discard the screw from the concentric flue connection.
  2. Remove the exhaust adapter ring. It is discarded for concentric venting.
  3. Install the concentric vent and make sure it is fully seated.
  4. Secure the vent pipe to the concentric flue connection with the supplied screws.
  5. Install the termination according to the manual diagrams.
  6. Slope the vent 1/4 in per foot (21 mm per m) back toward the appliance.
  7. Dispose of condensate per local codes.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rinnai Boiler codes

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 39. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.