Rinnai Boiler: Hydraulic separation and primary/secondary piping
Hydraulic separation and primary/secondary piping on a Rinnai boiler: Rinnai requires hydraulic separation between the boiler and the central heating system so that two or more circulators can run independently.
Applies to: Primary/secondary piping and hydraulic separators
How to fix hydraulic separation and primary/secondary piping: step by step
- Use hydraulic separation between the boiler loop and the central heating loop.
- Use closely spaced tees or a low loss header as the separator.
- For closely spaced tees, keep the separation at the header to no more than four pipe diameters.
- On a low loss header, install the relief valve and shut-off valves between the boiler and the header.
- When the boiler is used with a Rinnai air handler, follow the air handler manual for installation and performance details.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 57-58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.