Rinnai Boiler: Gas supply connection and leak check
Gas supply connection and leak check on a Rinnai boiler: Gas connection must be done by a licensed professional. Confirm gas type and supply pressure before connecting. Convert the gas type with the included conversion kit if it does not match the building supply (see Appendix section 14.5). Check supply pressure at the gas company's upstream location with all gas appliances running; it must be within the specification limits in section 3.4.
Applies to: Gas supply piping to the boiler
Common causes of gas supply connection and leak check
- Wrong gas type causes injury or unit damage
- Undersized gas line can lose pressure under full demand
How to fix gas supply connection and leak check: step by step
- Turn off 120V power and turn off the gas before working on the connection.
- Confirm the gas type matches the building supply; convert with the included kit if it does not.
- Check supply pressure upstream with all gas appliances operating and compare it to section 3.4.
- Install a sediment trap upstream of the gas controls.
- Install a manual gas shutoff valve between the gas supply and the boiler.
- Keep the gas ignition components protected from dripping, spraying and rain during operation and service.
- Purge debris from the gas line before connecting it to the boiler.
- Use approved connectors and a thread compound that resists LPG (propane).
- Check all joints for gas tightness with soap, leak detector solution or equivalent. Rinse with water after testing unless the solution is known to be non-corrosive.
- Do not operate the boiler if a leak is found until the leak is repaired.
- Size the gas line for the full demand of the boiler and all other gas appliances using section 6.3.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation manual, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.