Rinnai Boiler: Domestic hot water plumbing connections
Domestic hot water plumbing connections on a Rinnai boiler: DHW piping and components must be approved for potable water. Water connections must follow state and local plumbing codes. An approved pressure relief valve is required and must be accessible for service.
Applies to: DHW side plumbing
Common causes of domestic hot water plumbing connections
- Debris in the water line will damage the boiler
- Non-potable piping or boiler water treatment chemicals contaminate the DHW supply
How to fix domestic hot water plumbing connections: step by step
- Purge the water line of all debris and air before connecting.
- Do not connect the DHW to any piping previously used with a non-potable water heater.
- Do not introduce boiler water treatment or toxic chemicals into the DHW or potable piping.
- Confirm the water filter on the boiler is clean and installed.
- Connect the cold water supply to the DHW cold inlet connection on the bottom of the boiler, with an isolation valve.
- Connect the hot water supply to the DHW hot outlet connection on the bottom of the boiler, with an isolation valve.
- Install the DHW pressure relief valve per ANSI Z21.13 and ASME Section IV and keep it accessible.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation manual, p. 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.