Rinnai Boiler: DHW heat exchanger flush with vinegar
DHW heat exchanger flush with vinegar on a Rinnai boiler: Flush the plate heat exchanger when the LC reminder shows or in hard water areas. Failure to flush can damage the plate heat exchanger. Lime damage is not covered by warranty.
Applies to: All I-Series Plus condensing combi boilers
Common causes of dhw heat exchanger flush with vinegar
- Lime scale in the DHW plate heat exchanger
How to fix dhw heat exchanger flush with vinegar: step by step
- Shut off gas and turn off the DHW and CH buttons on the controller.
- Close the shutoff valves on the hot and cold water lines (V3 and V4).
- Connect the pump outlet hose H1 to the cold water line at service valve V2.
- Connect the drain hose H3 to the hot water line at service valve V1.
- Pour four gallons of undiluted food grade white vinegar into a pail.
- Place hose H3 and the pump inlet hose H2 into the cleaning solution.
- Open service valves V1 and V2.
- Remove the front panel and press the SW3 button on the PC board to start the flush mode.
- Run the pump and circulate the cleaner, then rinse and disconnect the hoses when complete.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 124. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.