Rinnai Boiler: Descale the plate heat exchanger with vinegar and rinse

Updated · by Aurora Star Tech Inc.

Descale the plate heat exchanger with vinegar and rinse on a Rinnai boiler: Vinegar flush for lime scale on the plate heat exchanger, followed by a rinse. Use undiluted food-grade white vinegar, about four gallons. Flush the boiler at least 1 hour at about four gallons per minute. Water treatment is recommended to prevent scale.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: I-Series Plus condensing combi boiler

How to fix descale the plate heat exchanger with vinegar and rinse: step by step

  1. Shut off the gas supply to the boiler.
  2. Turn off the DHW and CH buttons on the controller.
  3. Close the shutoff valves on the hot and cold water lines (V3 and V4).
  4. Connect the pump outlet hose (H1) to the cold water line at service valve V2.
  5. Connect the drain hose (H3) to the hot water line at service valve V1.
  6. Pour about four gallons of undiluted food-grade white vinegar into a pail.
  7. Place the drain hose (H3) and the pump inlet hose (H2) into the cleaning solution.
  8. Open service valves V1 and V2.
  9. Remove the front panel by taking out its two screws.
  10. Press the SW3 button on the PC board (lower left of the unit) to enter descaling mode.
  11. Use the up or down arrow to select dES, then press Select.
  12. Run the pump so the vinegar circulates for at least 1 hour at about 15.1 L/min.
  13. Press the DHW button to start the 60-minute countdown and watch for the time to count down.
  14. After the countdown, the display shows rnS. Stop the pump when done.
  15. Turn the pump off.
  16. Drain the vinegar: remove hose H3 from the pail and place it in a sink or outside. Close V2 and open V4 only, letting water flow for five minutes.
  17. Close V4 when draining is finished. Remove the in-line filter at the cold water inlet, clean out residue, refit it, and open V4.
  18. Close V1 and open V3.
  19. Press Select until End shows.
  20. Disconnect all hoses.
  21. Press Select to go back to dES, then press SW3 on the PC board to return to normal mode.
  22. Refit the front panel and restore the gas supply.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rinnai Boiler codes

Source: Rinnai I-Series Plus IP060160C installation and operation manual, pp. 128-130. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.