Rinnai Boiler: Change parameter A2 to allow higher exhaust temperatures
Change parameter A2 to allow higher exhaust temperatures on a Rinnai boiler: Set A2 to b only for CPVC, listed PP or stainless steel venting. Do not do this with PVC.
Applies to: I-Series Plus with CPVC, listed PP or stainless steel venting
How to fix change parameter a2 to allow higher exhaust temperatures: step by step
- Remove the front panel by taking out the two screws.
- Locate the PC board on the lower left side and press the SW1 left button.
- Scroll to parameter A2 and set it to b.
- Press the SW1 left button to exit to normal operation.
- Reinstall the front panel with the two screws.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.