Rinnai Boiler: Change altitude setting on the PC board
Change altitude setting on the PC board on a Rinnai boiler: Sets Parameter A3 for high altitude. Gas pressure does not need to be changed for high altitude when this parameter is used.
Applies to: I-Series Plus PC board, Parameter A3
How to fix change altitude setting on the pc board: step by step
- Remove the front panel by taking out the two screws that hold it.
- Locate the PC board on the lower left side of the unit.
- Locate the PC board buttons.
- Press the SW1 left button.
- Scroll to Parameter A3.
- Set Parameter A3 to the letter that matches the site altitude in the altitude table.
If the unit shows an error code, look it up: Rinnai Boiler codes
More commissioning tips for boiler
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 84. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.