Rinnai Boiler: Burner flame visual inspection
Burner flame visual inspection on a Rinnai boiler: The flame must cover the burner surface and burn clear, blue and stable. A yellow or green flame is unsatisfactory. Check the flame through the view ports on the burner.
Applies to: All I-Series Plus condensing combi boilers
Common causes of burner flame visual inspection
- Dirty burner or main burner or fan blades
- Flame color not clear blue
How to fix burner flame visual inspection: step by step
- Turn off and disconnect electrical power and allow the boiler to cool.
- Remove the front panel.
- Use a vacuum to remove dust from the main burner and fan blades. Do not use a wet cloth or spray cleaners.
- Do not open the burner cabinet or touch the burner surface.
- Restore power, fire the boiler and confirm a clear blue stable flame covers the burner surface.
- Clean the condensate trap and external drain of debris.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 117, p. 118. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.