Rinnai Boiler: Annual maintenance checks
Annual maintenance checks on a Rinnai boiler: Yearly service tasks for owner and licensed professional.
Applies to: I-Series Plus combi boiler
How to fix annual maintenance checks: step by step
- Inspect the vent system for blockages or damage, and clean the vent screen or room air filter if used.
- Clean dust and dirt from the fan and motor (motors are lubricated for life, no oiling).
- Clean the controller with a soft, damp cloth. Do not use solvents.
- Confirm pressure is 17-26 PSI; if low, add water until it is in range.
- Operate the pressure relief valve manually once a year, taking care with scalding discharge and making sure the discharge has a safe place to flow.
- Clean the heating system dirt trap, close the shut-off valves under the boiler first, then purge the air after reinstalling the filter.
- Clean the DHW inlet filter if DHW flow is dropping; close the DHW shut-off valves first.
- Check the expansion tank as recommended by the manufacturer.
- Check the condensate trap for sediment and remove it through the bottom plug without using a wrench on the drain.
- Confirm the condensate drain line is not blocked and the drain pump (if used) works.
- Flush the DHW plate heat exchanger in hard water areas, or when LC appears.
- For seasonal shutdown, close the shut-off valves below the boiler and drain the boiler to prevent freeze damage.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 116. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.