Rheem Heat Pump: Force a defrost test (PRL-JEC)

Updated · by Aurora Star Tech Inc.

Force a defrost test (PRL-JEC) on a Rheem heat pump: With the unit running in heat-pump mode, SW2 forces a defrost that runs until the termination temperature is reached or 14 minutes pass.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC

How to fix force a defrost test (prl-jec): step by step

  1. Set the thermostat to heat and make a heat call
  2. Press SW2 for one second with the unit running in heat-pump mode
  3. Watch the unit enter defrost; press SW2 again to stop the test early
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Heat Pump codes

Models

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

Source: Rheem PRL-JEC Installation Instructions, 8.4-8.5 Defrost Test Mode. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.