Rheem Furnace: Upflow with vertical vent: condensate drain and intake conversion
Upflow with vertical vent: condensate drain and intake conversion on a Rheem furnace: Converts the furnace for upflow with vertical vent using only parts from the parts bag. Install the intake coupling, choose the right or left drain side, and set up the condensate drain using tube C or hose A.
Applies to: Upflow with vertical vent; parts bag only
How to fix upflow with vertical vent: condensate drain and intake conversion: step by step
- Install the intake coupling in the top plate.
- Choose the right or left drain side.
- For the drain side, remove and discard the 7/8 in. plug from the jacket side, then drill two 1/8 in. holes for the condensate drain coupling.
- Install the condensate drain coupling with two #8 x 1/2 in. screws, barbed fitting pointed into the vestibule.
- Install the hose clamp on the hose over the condensate drain coupling.
- Left drain: attach pre-installed hose A to the condensate drain coupling.
- Right drain: cut tube C to the cabinet width, attach it to hose A with a hose clamp, then attach the tube C assembly to the condensate drain coupling and clamp the hose over the coupling.
- Use soapy water to ease hose and tube assembly.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: 96V series installation instructions, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.