Rheem Furnace: Single-stage thermostat on a two-stage furnace: auto staging

Updated · by Aurora Star Tech Inc.

Single-stage thermostat on a two-stage furnace: auto staging on a Rheem furnace: With only W1 wired, the furnace can step itself up to high fire after a set time.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces

How to fix single-stage thermostat on a two-stage furnace: auto staging: step by step

  1. Set S2-10 / S2-11: OFF-OFF normal two-stage (default); ON-OFF 10 min on low then high; OFF-ON 15 min; ON-ON 20 min.
  2. A W2 call still forces high stage even with auto staging on.
  3. Communicating systems ignore the dipswitches; staging is set at the thermostat.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

96MDV040B30A96MDV060B30A96MDV070B30A96MDV085C50A96MDV100C50A96MDV115D50AR96VA0401317MSAR96VA0601317MSAR96VA0701317MSAR96VA0851521MSAR96VA1001521MSAR96VA1151524MSA

Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, 12.G p.91. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.