Rheem Furnace: Setting gas manifold pressure

Updated · by Aurora Star Tech Inc.

Setting gas manifold pressure on a Rheem furnace: You set manifold pressure after you have confirmed that supply pressure is within limits. Do not adjust the regulator on a bad supply, or you will chase your tail. I always read supply first with a calibrated manometer, then work on the manifold for both high fire and low fire. The regulator only has so much range, and when the flow needs a big change, the right answer is a different orifice, not cranking the screw. Gas work is for a licensed gas technician.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 96V and 96MDV gas furnaces

Common causes of setting gas manifold pressure

  • Supply pressure outside the limits for adjustment
  • Manifold pressure out of spec for the fuel type
  • Regulator out of range for a large flow change
  • Weak or lazy flame after conversion or altitude change

How to fix setting gas manifold pressure: step by step

  1. Use a calibrated manometer to read the gas supply pressure
  2. Confirm supply is within limits: maximum 10.5 in w.c. natural gas or 13.0 in w.c. LP, minimum 5 in w.c. natural gas or 11 in w.c. LP for adjustment
  3. Set manifold pressure to the high-fire and low-fire values for the gas type
  4. To adjust, remove the regulator cap; turn the screw clockwise to raise pressure or counterclockwise to lower it
  5. Replace the regulator cap securely
  6. Keep final manifold pressure within 0.3 in w.c. of the specified value
  7. For large flow changes, change the burner orifice size instead of the regulator
  8. Leak-check any disturbed fittings with an approved detector
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

96V

(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100

96MDV

96MDV06096MDV07096MDV08596MDV100

Source: 96V installation instructions, p. 103. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977