Rheem Furnace: One-hour lockout causes
One-hour lockout causes on a Rheem furnace: A one-hour soft lockout starts when any of these occur: flame not detected after four ignition trials; flame lost five times in one heat call; undesired flame detected (one hour starts after flame is gone); dead blower detected (main limit open more than 150 seconds); unexpected voltage on the gas valve circuit that goes away when the inducer shuts off; or a water sensed condition that clears and returns within five minutes of the next heat attempt in the same heat call. The display alternates between "10" and the fault code. The lockout clears automatically after one hour.
Applies to: R96V furnace
Common causes of one-hour lockout causes
- Failed ignition trials
- Repeated flame loss
- Undesired flame
- Dead blower
- Gas valve circuit voltage
- Recurring water sensed condition
How to fix one-hour lockout causes: step by step
- Read the fault code shown alternately with "10".
- Correct the underlying fault using the matching code entry.
- Clear the original fault and cycle power to the unit, or wait one hour for the automatic reset.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
Source: Rheem 96V series installation instructions, p. 118. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.