Rheem Furnace: Natural gas at high altitude: derate
Natural gas at high altitude: derate on a Rheem furnace: No high altitude pressure switch changes are needed. Derate the input by 4% per thousand feet above 2,000 ft. Factory orifices are sized for 1100 BTU/ft3 at sea level; regional heating values may remove the need to change them except at extreme altitudes. Above 2,000 ft, follow local codes or NFGC/CSA B149.1.
Applies to: Natural gas above 2,000 ft
How to fix natural gas at high altitude: derate: step by step
- Derate the input 4% per 1,000 ft above 2,000 ft.
- Check the local gas heating value before changing orifices.
- Follow local codes, or NFGC / CSA B149.1 where no local code applies.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: 96V series installation instructions, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.