Rheem Furnace: Natural gas at high altitude: derate and orifice check
Natural gas at high altitude: derate and orifice check on a Rheem furnace: No high altitude pressure switch change is needed. The input must be derated 4 percent per 1,000 ft above 2,000 ft. Factory orifices are sized for a sea level natural gas heating value of 1100 BTU per cubic ft, so a regional lower heating value may make an orifice change unnecessary except at extreme altitudes. Installation above 2,000 ft must follow local codes or the National Fuel Gas Code (ANSI Z223.1/NFPA 54), or CSA B149.1 in Canada.
Applies to: 96V and 96MDV natural gas furnaces above 2,000 ft
How to fix natural gas at high altitude: derate and orifice check: step by step
- Find the local natural gas heating value (BTU per cubic ft) from the gas supplier.
- Calculate the gas flow per hour: sea level input per burner divided by the regional heating value (example: 14000 / 900 = 15.56 cu ft per hour).
- Use the National Fuel Gas Code Annex E tables (E.1.1(a) for sea level orifice, E.1.1(d) for elevation de-rate) or the supplemental orifice chart (Table 14) to pick the orifice.
- Reduce the sea level input by 4 percent per 1,000 ft and confirm the orifice size for that reduced input.
- Change the burner orifice only if the calculation shows it is needed. Re-check the input rate after any change.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: Rheem 96V series installation instructions, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.