Rheem Furnace: Massachusetts CO detector and signage rules for sidewall horizontal venting
Massachusetts CO detector and signage rules for sidewall horizontal venting on a Rheem furnace: In Massachusetts, sidewall horizontally vented gas equipment with the exhaust termination less than 7 feet above finished grade (including over decks and porches) needs hard-wired CO detectors with battery backup on the floor where the appliance is installed, plus CO detectors on each additional level. A metal or plastic sign reading GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS must be mounted 8 feet above grade in line with the vent. Detectors must meet NFPA 720 and ANSI/UL 2034 and be IAS certified. If the detectors cannot be installed at completion, a battery CO detector must be used during the 30-day allowance.
Applies to: Sidewall horizontal vent installations in Massachusetts
How to fix massachusetts co detector and signage rules for sidewall horizontal venting: step by step
- Confirm the exhaust termination height above finished grade.
- Install hard-wired CO detectors with battery backup on the appliance floor and on each additional level.
- If not possible at completion, install battery CO detectors and finish the hard-wired installation within 30 days.
- Mount the required warning sign 8 feet above grade in line with the exhaust terminal.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
More commissioning tips for furnace
Source: 96V series installation instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.